0 66 31 / 911 54-0
Type: DTTM
Three - phase isolating transformers for medicine
To supply IT - systems in medical rooms;
according to DIN/VDE 0107
Isolating transformer according to DIN/VDE 0551-EN60742
protection class I, safety earth connection
type of protection: IP00 (suitable for installation up toIP23)
shielding winding between PRI- and SC-winding
SEC - winding with brought-out neutral point
to monitor insulation built-in thermal cut-out
(break-contact)
vertical version
frequency: 50/60 Hz
insulation class: T40/F
type of protection: IP00 (suitable for installation up toIP23)
impregnated against rust with resin
PRI-voltage: 400V
SEC-voltage: 230V
vector group: Yyn0
no-load current impedance voltage the transformers are also available with other voltages or vector groups corresponding to your wishes
Leistung power kVA | Best. (BV) -Nr. order No. | Maße / dimensions (mm) | Gewicht weight (kg) | Download | ||||||
A | B | C | D | E | F | GØ | ||||
2,0 | 50473 | 300 | 140 | 325 | 210 | 140 | 110 | 11 | 30,5 | Datenblatt |
2,5 | 50474 | 300 | 155 | 325 | 210 | 140 | 125 | 11 | 36,0 | |
3,2 | 50475 | 300 | 165 | 325 | 210 | 140 | 135 | 11 | 42,0 | |
4,0 | 50476 | 335 | 175 | 365 | 230 | 160 | 145 | 11 | 53,0 | |
5,0 | 50477 | 360 | 175 | 395 | 250 | 170 | 145 | 11 | 58,0 | |
6,3 | 50478 | 360 | 190 | 395 | 250 | 170 | 160 | 11 | 68,0 | |
8,0 | 50479 | 360 | 205 | 395 | 250 | 170 | 175 | 11 | 78,0 |