0 66 31 / 911 54-0
Type: DHT
three - phase high voltage transformers
according to DIN/VDE 0532
vertical version
separate windings
PRI - voltage : 400 V
SEC - voltage : 4000 V
vector group: Dyn5
frequency: 50/60 Hz
insulation class: T40/B
type of protection IP00 (suitable for installation up to IP23)
built - in thermal cut-out
resin - encapsulated PRI-winding
impregnated against rust with resin
the transformers are also available with other voltages or vector groups corresponding to your wishes
Leistung power kVA | Best. (BV) -Nr. / order No. | PRI-Spannung voltage | SEC-Spannung voltage | Maße / dimensions (mm) | Gewicht weight (kg) | Download | |||||
A | B | C | D | E | FØ | ||||||
6,3 | 51760 | 400 | 4000 | 500 | 190 | 450 | 355 | 155 | 13 | ||
8 | 51761 | 400 | 4000 | 500 | 190 | 450 | 355 | 155 | 13 | ||
10 | 51762 | 400 | 4000 | 620 | 275 | 520 | 540 | 225 | 18 | ||
15 | 51763 | 400 | 4000 | 620 | 275 | 520 | 540 | 225 | 18 | ||
20 | 51764 | 400 | 4000 | 680 | 285 | 630 | 620 | 225 | 18 | ||
25 | 51765 | 400 | 4000 | 680 | 285 | 630 | 620 | 225 | 18 | ||
32 | 51766 | 400 | 4000 | 740 | 285 | 680 | 620 | 225 | 18 | ||
40 | 51767 | 400 | 4000 | 740 | 285 | 680 | 620 | 225 | 18 |